50 amp service
I have been having trouble with the main breaker tripping sometimes. I discovered that the power center is a model 7300 designed and recommended for use only with 30 amp service.
The literature on the 360rkds I have indicates it has 50 amp service. The cord is a 50 amp cord. This is a real problem and safety hazard.
I have emailed (thursday late) OR and asked for a replacement with the proper 50 amp power center. I have not gotten a reply but they close very early on Friday.
I will call them Monday and hope they will solve this problem.
Steve.
We're leaving on a 9 day trip tomorrow with our new 357 RLDS with 50 amp service. I'll need to check that out. Hope Open Road knows that 50 amp services require 50 amps panels to avoid fires. Wonder how many were made this way? (Limited production errors or standard practice?)
50 amp power center
installed 50 amp unit sent by open road. Works great. No more elec. problems so far. The 30 amp power center was set up in a crazy way using a separate breaker box with a 50 amp main and 30 amp service directed to the 30 amp power unit and a 20 amp line to the microwave. I have all in the 50 amp power center now, the way it is supposed to be set up. Steve.